Safeline UNIVERSAL+ integral product range

Comparison of Integral Equipment

Analyze the technical differences between models to choose the protection and control your installation truly needs.

UNIVERSAL+ 7WR Model (3-year warranty)
7WR-M1 7WR-M2 7WR-M5 7WR-5PM 7WR-K1 7WR-K0 7WR-K
Slave MCB Current
2P and 4P up to 63A 2P and 4P up to 250A 2P and 4P up to 10,000A 2P and 4P up to 63A 2P and 4P up to 63A 2P and 4P up to 63A 2P and 4P up to 63A
Automatic Reset
Programmable Multi-protections
30 protections
(High precision)
30 protections
(High precision)
30 protections
(High precision)
29 protections 29 protections 28 protections 13 protections
Electrical Grid Analysis Level
Professional Professional Professional Advanced Advanced Basic
(No graphics)
Essential
(No graphics)
Network Analysis
RMS and Peak Residual Current Protection
Yes. Ultra-immunized
(Type A/B)
Yes. Ultra-immunized
(Type A)
Yes. Ultra-immunized
(Type A)
Yes. Ultra-immunized
(Type A)
Yes. Ultra-immunized
(Type A)
Yes. Ultra-immunized
(Type A)
Yes. Ultra-immunized
(Type A)
THD Harmonic Distortion Alarm and Measurement
7-Channel Oscilloscope
Event Recorder Oscilloscope with Pre-trigger
Differential Current Oscilloscope and Real-Time Graph
64 Harmonic and 7 Channel Spectrum Analysis
Graphical Measurement History
Graphical Recorder of 300 Logs with 12 Channels
Historical LOG Recorder
Automatic Data Transmission to Remote Server
Independent Disconnection Counters
Maximum and Minimum Measurement Logs
Relay Outputs and Digital Inputs
10 Out, 10 In, 4 remote Out LAN/WAN 10 Out, 10 In, 4 remote Out LAN/WAN 10 Out, 10 In, 4 remote Out LAN/WAN 10 Out, 10 In, 4 remote Out LAN/WAN 10 Out, 10 In, 4 remote Out LAN/WAN 2 Out, 2 In 2 Out, 2 In
Temperature and Humidity Sensors
1 local, 6 remote 1 local, 6 remote 1 local, 6 remote 1 local, 6 remote 1 local, 6 remote 1 local 1 local
PC and Server Software Compatibility
DataWatchPro and Safeline Web Services DataWatchPro and Safeline Web Services DataWatchPro and Safeline Web Services DataWatchPro and Safeline Web Services DataWatchPro
Ultra-fast Disconnection
High Security
Visualization, programming, and control from a web browser via Internet or intranet, without additional software.
Integration into SCADA systems and IoT platforms via Modbus TCP/IP and TCP/IP/HTTP commands from the integrated web server.
Programming protected by security key.
Default factory configuration.
Configurable language: Spanish or English.
Manual disconnection with or without key.
Programmable RMS visualization averaging: 100, 200, 300, 400, and 500 ms.
Integrated web server.
Standards: EN 60947-2 (Annex B):2018, UNE-EN 62053-22:2003 CLASS 0.5S, EN 62053-23:2003 CLASS 2, UNE 20-600-77, EN 50550:2011 (see manual)